Описание оборудования | |
|---|---|
| Printed circuit board module 2 NAMUR inputs and 1electronic output | |
General specifications | |
| Slave type | A/B slave |
Indicators/operating means | |
| LED PWR/FAULT | dual LED green/red LED 1 green: AS-Interface voltage OK LED 1 red: communication error or address is 0 LED 1 green/red flashing: short-circuit or lead breakage |
| LED IN | 2 LEDs yellow; LED 2 yellow illuminated: switching state IN1 ON, otherwise OFF LED 3 yellow illuminated: switching state IN2 ON, otherwise OFF |
Electrical specifications | |
| Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
| Rated operating current | ? 40 mA (without sensors) / max. 150 mA |
| Protection class | III |
Input | |
| Number/Type | 2 inputs for NAMUR Sensors |
| Supply | from AS-Interface |
| Voltage | 8 V |
| Input current | ? 8 mA (limited internally) |
| Switching point | OFF ? 1.2 mA ON ? 2.1 mA according to DINEN60947-5-6 |
Output | |
| Number/Type | 1 electronic output, switched low, overload and short-circuit proof, lead breakage and short-circuit monitored |
| Supply | from AS-Interface |
| Current | max. 100mA |
| Voltage | 21 ... 31 V |
Standard conformity | |
| Degree of protection | EN60529:2000 |
| AS-Interface | EN62026-2:2013 |
Programming instructions | |
| Profile | S-D.A.E |
| IO code | D |
| ID code | A |
| ID1 code | 7 |
| ID2 code | E |
| Data bits (function via AS-Interface) | input output |
| Parameter bits (programmable via AS-i) | function |
Ambient conditions | |
| Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Mechanical specifications | |
| Degree of protection | IP20 (completely fitted) according to EN 60529 |
| Connection | screw terminal strip max. conductor cross section 1mm2 |
| Mass | 20 g |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |